HS51 Series Smoke & Heat Detector
HS51 Series Smoke & Heat Detector
Designed to comply with UL539 standards
2 wire or 4 wire optional Fixed temperature 57ºC,135F heat sensor
Non-polar power input Extended warranty
  • Description
  • Characteristic
  • Others
  • Download
HS51P-2  2 Wire Smoke & Heat Detector
HS51P-4   4 Wire Smoke & Heat Detector

Features

Designed to comply with UL539 standards
2 wire or 4 wire optional
Fixed temperature 57ºC,135F heat sensor
Non-polar power input
Extended warranty
Easy Installation and maintenance

Specifications

Model HS51P-2 HS51P-4
Operating Voltage DC9~35V
Standby Current 55uA 12mA(NC),  2mA(NO)
Alarm Current 22mA@DC12V, 40mA@DC24V 3mA(NC), 15mA(NO)
Alarm Output Remote LED indicator Relay output (N.O/ N.C) and LED flash
Smoke Alarm Density 2.06%/ft
Alarm Temperature 57ºC (135F)
Detecting Area 80 square meter (with the installation height of 6m-12m), and 60 square meter (with the installation height less than  6m)
Installation Method Ceiling Mounted
Operating Temperature -10°C ~ +55°C
Operating Humidity ≦95%RH
Dimensions 100mm(Dia)x46mm(H)
Contact us
Email:info@phsecu.com
Tel:+86-755-83239748
Feedback Form
Powered by LY Network